kVA Calculator – kVA, Amps & kW (Single & Three-Phase)

Convert between kVA, amps and kW for single-phase and three-phase systems at any voltage. The calculator also gives real power, reactive power (kVAR) and the next standard transformer or generator size.

Formula checked 23 Oct 2026 Free · no sign-up
Was this calculator helpful?

Found a bug or have a suggestion?

Leave it here and we will fix it and reply to you.

Embed this calculator on your website (free)

Copy this code into your page. It stays free and updates automatically.

How to use the kVA calculator

  1. Choose what to calculate: kVA from amps, amps from kVA, or convert kW to kVA.
  2. Pick single-phase or three-phase and enter the voltage. For three-phase, use the line-to-line voltage.
  3. Enter the power factor to get real power in kW (0.8 is standard for generators).

The formulas

Single-phase: kVA = V × A ÷ 1,000 A = kVA × 1,000 ÷ V Three-phase: kVA = √3 × V × A ÷ 1,000 A = kVA × 1,000 ÷ (√3 × V) Real power: kW = kVA × PF Reactive: kVAR = √(kVA² − kW²)

Worked examples

  • 100 A at 480 V three-phase: 1.732 × 480 × 100 ÷ 1,000 = 83.1 kVA → a 100 kVA transformer.
  • 50 A at 240 V single-phase: 240 × 50 ÷ 1,000 = 12 kVA.
  • 75 kVA transformer, 208 V three-phase: 75,000 ÷ (1.732 × 208) = 208 A.
  • 80 kW load at PF 0.8: 80 ÷ 0.8 = 100 kVA, with 60 kVAR of reactive power.

Full-load amps for common transformer sizes

kVA208 V 3-ph240 V 3-ph480 V 3-ph400 V 3-ph
1541.6 A36.1 A18.0 A21.7 A
3083.3 A72.2 A36.1 A43.3 A
45124.9 A108.3 A54.1 A65.0 A
75208.2 A180.4 A90.2 A108.3 A
112.5312.3 A270.6 A135.3 A162.4 A
150416.4 A360.8 A180.4 A216.5 A
300832.7 A721.7 A360.8 A433.0 A

Understanding power factor

Power factor (PF) is the ratio of real power to apparent power. Purely resistive loads such as heaters and incandescent lamps have a PF of 1.0, so kVA equals kW. Motors, transformers and many electronic power supplies draw extra current that does no useful work, lowering the PF to around 0.8–0.9. A low power factor means larger cables, transformers and generators for the same useful power, and many utilities charge commercial customers a penalty when PF drops below about 0.9. Capacitor banks or drives with active front ends can correct it.

Sizing tips

  • Leave headroom: size for 125% of continuous loads, matching NEC practice for conductors and overcurrent protection.
  • Motor starting: direct-on-line motors draw 6–8 times their running current briefly; generators and small transformers must handle that inrush.
  • Single-phase loads on three-phase supplies: balance them across the phases, otherwise one phase reaches its limit first.
  • Check the nameplate: always use the transformer or generator manufacturer’s ratings for final design and have a licensed electrician verify it.

Single-phase vs three-phase

Homes in North America usually have a 120/240 V single-phase service, while commercial buildings use 208 V or 480 V three-phase. In Europe, Asia and Australia, 230 V single-phase and 400 V three-phase are standard. Three-phase power delivers √3 (about 1.73) times as much power for the same current per conductor, which is why larger motors, chillers and industrial equipment use it.

Frequently asked questions

How do I convert amps to kVA?

Single-phase: kVA = volts × amps ÷ 1,000. Three-phase: kVA = √3 × volts × amps ÷ 1,000, using the line-to-line voltage. 100 A at 480 V three-phase is 1.732 × 480 × 100 ÷ 1,000 = 83.1 kVA.

How do I convert kVA to amps?

Single-phase: amps = kVA × 1,000 ÷ volts. Three-phase: amps = kVA × 1,000 ÷ (1.732 × volts). A 75 kVA transformer at 208 V three-phase has a full-load current of 208 A.

What is the difference between kVA and kW?

kVA is apparent power (volts × amps); kW is the real power that does work. kW = kVA × power factor. With a power factor of 0.8, a 100 kVA generator delivers 80 kW.

Why are generators rated in kVA?

Because the alternator’s heating depends on current, not on the load’s power factor. Generators are usually rated at a 0.8 power factor, so the kW rating is 80% of the kVA rating.

What size transformer do I need?

Add up the load in kVA, allow 20–25% for growth and continuous loading, and choose the next standard size (for example 15, 30, 45, 75, 112.5, 150, 225, 300 or 500 kVA for three-phase dry-type units).

What is kVAR?

kVAR is reactive power, which flows back and forth in motors and transformers without doing work. kVA² = kW² + kVAR²; power-factor correction capacitors reduce kVAR.

How we checked this calculator

We test this tool against worked examples before every release (last check: 23 Oct 2026, version 1.0.0). Results are estimates for planning — confirm critical figures with your supplier or a qualified professional.